DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
New correlations predicting the local boiling heat transfer coefficients for vertical flow over a tube bundle have been developed. These correlations were developed for three different classes of tubes: smooth, low-finned, and Turbo-BII HP. These correlations are based on experiments with refrigerants R-134a, R-507A, and R-410A, at a saturation temperature of 4.4°C (40°F). Each one accounts for the local flow structure and/or local geometry particular to each tube. Each one also uses a void fraction model designed specifically for vertical two-phase flow in a tube bundle as an integral part of the correlation. The correlations have been compared to recent local bundle boiling data and show good agreement to within ± 20%.