DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
The present paper investigates transient overvoltages on ac induction motors when connected through a cable of arbitrary length to IGBT-PWM inverters. Considering classical transmission line analysis, and traveling-wave analysis with zero initial charges on cables, these transient over voltages are about twice the dc link voltage with a short rise time of about 200 ns. Nevertheless for long cables, these transient overvoltages may reach 3 or 4 p.u. The target of the present study is to define the properties of these overvoltages, their dependency on the installation parameters, and to present a combination of two measures (series reactors and capacitor-resistor termination impedance) to reduce the voltage rise du/dt and the over voltages at the motor terminals. Experimental results performed on a 3 kW drive are presented.