DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
The current source thyristor inverter is still today a suitable choice for supplying high power adjustable speed drives for pumps or compressors. This paper presents a 12-pulse LCI (load commutated inverter) synchronous drive for a 20 MW compressor, it focuses on the following main aspects: modeling of the complete drive system, numerical simulation and comparison between calculated and measured values of the pulsating torque components in steady-state operations. The modeling of the six-phase synchronous motor is obtained by using a new virtual test-platform for large electrical machines. The pulsating torque components are measured in real time with a digital transient torque measurement device.
Drazen Dujic, Andrea Cervone, Tianyu Wei
Drazen Dujic, Andrea Cervone, Tianyu Wei