DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
We consider real-time control systems that consist of a controller that computes and sends setpoints to be implemented in physical processes through process agents. We focus on systems that use commercial off-the-shelf hardware and software components. Setpoints of these systems have strict real-time constraints: Implementing a setpoint after its deadline, or not receiving setpoints within a deadline, can cause failure. In this paper, we address delay faults: faults that cause setpoints to violate their real-time constraints. We present Axo, a fault-tolerance protocol that guarantees safety and improves availability for a class of such systems that exhibit two main properties: the setpoints must have a known validity horizon, and process agents must be capable of handling duplicate setpoints. To reason about delay faults, and consequently design Axo, we present an abstraction of a controller; the abstraction applies to a wide range of real-time control systems. We prove guarantees of safety and availability. Finally, we present an implementation of Axo and the results of the tests performed with Commelec, a real-time control system for electric grids.
Mario Paolone, Willem Lambrichts