DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
The concept of MVDC collection network for renewable applications requires a high efficiency DC-DC converter to connect low voltage sources to the medium voltage network. The accurate measurement of low power losses is not possible with traditional electrical input-output power measurements. This paper adopts and extends a transient calorimetric method suited for the measurement on such converters. It is shown experimentally that this method can be applied to the measurement of the losses of an oil-immersed DC-DC converter. The maximum efficiency of the 83 kW, 1.2 to 6.6 kV prototype is measured at 99.16 ±0.04% (99.12…99.20%).