Ask any question about EPFL courses, lectures, exercises, research, news, etc. or try the example questions below.
DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
This paper deals with the modeling of multi-winding transformers. Based on the real example of a railway DC - supply, a modeling methodology is presented as the original part of the paper. Afterwards two application examples of multi-winding phase shifting transformers (18 and 24 pulse) are described, these applications have been simulated using the SIMSEN simulation software package [1,2]. Harmonics analysis of simulation results (elimination of low order harmonics 5, 7, 11, 13) has validated the proposed methodology.