DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
By using the electromagnetic time reversal (EMTR) theory, the paper studies its properties in order to derive a new fault location method to be used in power networks. It is shown that, in the reversed-time stage, the current signal observed at the true fault location can be clearly distinguished since it appears as a time-delayed copy of the back-injected fault-originated transient signal. Then, based on this similarity property, a fault location method is derived. Finally, the method is numerically validated with reference to a reproducible simulated power network composed of an inhomogeneous multi-conductor transmission-line system.