DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
A very high accuracy, straight vibrating tube type of density flow meter has been used online to measure oil concentraiton of flowing R-134a/oil mixtures. The calibrations covered oil concentrations from 0-6 wt.% oil over the temperature range from -9.4 to 5.9°C. The oil concentrations were correlated statistically as a function of density, temperature and liquid compressibility to an average error of 0.09 wt.% oil with a 95% confidence limit of 0.21 wt.% oil. In addition, a simplified method not requiring calibration tests was developed for general industrial application of the density flowmeter to any refrigerant-oil mixture combination, with an average error of 0.22 wt.% oil and 95% confidence limit of 0.67 wt.% oil for the present data set.