DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
New saturated critical heat flux (CHF) data have been obtained experimentally in two different multi-microchannel heat sinks made in copper with three low pressure refrigerants (R134a, R236fa, R245fa). one of the test sections has 20 parallel rectangular channels, 467 mu m wide and 4052 mu m deep while the second has 29 channels, 199 mu m wide and 756 mu m deep. The microchannels are 30 mm long in the flow direction where a 20 mm length in the middle is heated with an electrical resistance deposited on a silicon plate. Base CHF values were measured from 37 to 342 W/cm(2) for mass velocities from 100 to 4000 kg/m(2) s. When increasing the mass velocity, CHF was observed to increase while the rate of increase was slower at high velocities. While CHF increased moderately with large inlet subcooling (e.g. 20 K) in the H = 4052 mu m channels, inlet subcooling seemed to play less a role as the channel size decreased. CHF showed reversed tendency with increasing inlet saturation temperature (10
Andreas Mortensen, Léa Deillon, Alejandra Inés Slagter, David Hernandez Escobar
Ian Smith, Katrin Beyer, Bryan German Pantoja Rosero, Mathias Christian Haindl Carvallo
Danick Briand, Nicolas Francis Fumeaux