DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
Recent advances in the application of nontraditional methods and procedures for offline diagnosis and online monitoring of new and service-aged power transformers are discussed. Advanced offline methods are based on the main operational stresses (electrical, mechanical, thermal) and on typical failure modes: measurement of polarisation and depolarisation currents, electrical detection of partial discharges and measurement of the transfer function. A pilot installation of an online monitoring system on a strategically important transformer is described. The measured data of the built-in sensors (e.g. load, temperatures, gas and moisture in oil, overvoltages) are analyzed using a model-based software approach with an adaptive threshold to define faulty conditions