Ask any question about EPFL courses, lectures, exercises, research, news, etc. or try the example questions below.
DISCLAIMER: The Graph Chatbot is not programmed to provide explicit or categorical answers to your questions. Rather, it transforms your questions into API requests that are distributed across the various IT services officially administered by EPFL. Its purpose is solely to collect and recommend relevant references to content that you can explore to help you answer your questions.
An extensive database has been collected for the evaporation of two hydrofluorocarbon refrigerants (HFC- 134a and the zeotropic mixture HFC- 407C) and the natural refrigerant ammonia (R-717). A model to predict the onset of nucleate boiling has been successfully developed to differentiate pure convective evaporation from mixed convective and nucleate boiling heat transfer during horizontal evaporation inside a horizontal tube of 14mm I.D. The analysis of the Stratified, Stratified-Wavy and mainly Annular flow patterns during evaporation with differente heat flux ranges showed very accurate results in terms of mean local heat transfer coefficient using this new onset of nucleate boiling criterion.